Technical Specification

A full technical specification of the Fire Beam and associated components can be seen below, answering most of the questions you may have. Beneath this we have also included a comparison chart which shows how the Fire Beam performs when compared side by side to its competitors.
Electrical Specifications:
Supply Voltage   10.2 to 40 VDC
Supply Current   3mA (constant current) in all operational states
 
Environmental Specifications:
Temperature   -10°C to +55°C
Humidity   10 to 95% RH Non-condensing
Protection Index   IP65 when suitably mounted and terminated
 
Mechanical Specifications:
Beam Head   180mmH x 155mmW x137mmD Weight 1.1Kg
Controller   185mmH x 120mmW x 62mmD Weight 0.55Kg
Mid Range Kit   293mmH x293mmW x 5mmD Weight 0.8Kg
Long Range Kit   394mmH x 394mmW x 5mmD Weight 1.8Kg
Adaptor Plate   270mmH x 250mmW x 5mmD Weight 0.6Kg
(mounts the Beam Head onto Unistrut)
 
Optical Specifications:
Optical Wavelength   870nm
Maximum Angular Alignment   ±15°
Maximum Angular Misalignment   (static not auto-aligning)
Beam Head ±0.75°  /  Reflector ±2°
 
Operational Specifications:
Protection Range
Standard Fire Beam   5 to 40 metres
Mid Range Kit   40 to 80 metres
Long Range Kit   80 to 100 metres
 
Alarm Sensitivity Levels
25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB))
 
Alarm Condition:
Obscuration drops to below pre-defined sensitivity level.
Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default setting is 10 seconds)
 
Alarm Indication:
Controller Status - FIRE
Controller Red Flashing LED 0.5 Second
Head Red Flashing LED 1 Second
Alarm Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
 
Test / Reset Features:
Beam test function by controller
Alarm latching / auto-reset selectable (default auto-reset)
Alarm reset in latching mode by controller reset function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.
 
Fault Sensitivity Level:
90%
 
Fault Condition:
Obscuration drops to below the fault sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
Commissioning modes, Pre-Alignment and Auto Alignment
Beam turned off during Beam Maintenance (auto resets in 8 hours to normal)
Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
 
Fault Indication:
Controller Status - FAULT
Controller Yellow Flashing LED 1 Second
Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC
 
Normal Condition:
Obscuration level is above the Alarm sensitivity level
Controller Status - NORMAL
Controller Green Flashing LED 1 Second
Programmable on/off
Head Green Flashing LED 1 Second
Programmable on/off
 
Auto-Align / Beam Contamination Compensation:
Auto-align during normal operation if obscuration drops below 90% (doesn't effect normal operating mode)
Beam Contamination Compensation 4 hour monitoring. Compensation data available at the controller

 